G99 / Grid Code – Fault Ride Through / Fast Fault Injection
Fault
Ride Through studies are a basic requirement of Type B and C / D
generators, to demonstrate ride through for a fault lasting 140ms. The
basic process is the same in all cases, but the retained voltages and
recover rate differs slightly between the cases and generation type. For
Grid Code studies, there are some extra requirements for longer
duration events, for differing levels of voltage depression on the
network.
At the moment the requirement is to carry these out as
RMS (ideally unbalanced) simulations. However, NG ESO are moving to
require these to be carried out as detailed EMT studies, to ensure that
the FRT response is a true reflection of the generator capability.
Fast
Fault Current Injection is part of this process, and specifically
associated with 3-phase faults. It should meet a specific magnitude in
order to satisfy the requirement.
There are a couple of
interesting anomalies in both G99 and the Grid Code, that are ‘known’
about, but have not been corrected. 1) For 2-phase faults it is
impossible to get a retained voltage of less than 50%. 2) For an
impedance earthed MV system a bolted fault on the MV, usually wont cause
a big enough voltage depression on the LV system to trigger the FRT
response.