• Home
        • Generation
        • Aurora works across a wide range of traditional power generation systems, from small CHP units up to large industrial power generation facilities. We have extensive experience in considering synchronous generators fault contribution into the network, as well as considering issues such as dynamic response and transient stability of synchronous generators.

        • Renewables & Energy Storage
        • Aurora provides a range of services to the Renewables and Battery Energy Storage Systems industries, and can provide advice on analysis on greenfield developments or integration into existing brownfield industrial facilities. We specialise in providing grid simulation and G99 compliance studies to support renewable connections to the UK network, and other European networks.

        • Transmission & Distribution
        • Aurora has extensive experience in the transmission and distribution sector, dealing with private 11kV and 33kV networks, iDNOs and DNOs and National Grid, for a variety of different design and analysis applications.

        • Oil, Gas and Petrochemical
        • Aurora has extensive experience in the Oil & Gas industry, and has undertaken a wide range of design activities, concept studies and simulation studies to support many large international EPC companies and service companies.

        • Industrial
        • Aurora works in light and heavy industry providing a range of services to help plant owners analyse and understand their networks, identify weak spots, providing guidance on system loadings, fault levels, earthing, protection coordination and arc flash.

        • Data Centres
        • Aurora has worked on a number of large data centres, providing a range of services to support existing specialist companies in this area, such as system analysis for fault levels, harmonic analysis, protection coordination and arc flash analysis.

        • Building Services
        • Aurora works in Building Services industry to support multiple M&E contractors in development of the HV aspects of their design, or integration of renewable technologies like roof top solar.  Services include system analysis for fault levels, harmonic analysis, protection coordination and arc flash analysis.

        • Water
        • Aurora has extensive experience in the water industry and has worked fs, identify weak spots, providing guidance on system loadings, fault levels, protection coordination, motor starting earthing and arc flash. We also have extensive experience in helping water companies integrating renewalbe power and battery storge technologies into their sites.

        • Power System Analysis
        • Load flow, fault analysis, P28/2 voltage disturbance including flicker and transformer inrush, G5.5 Harmonics, G99 Grid studies, protection coordination, arc flash, dynamic and transient studies and electromagnetic transients.

        • Power System Design
        • Concept selection, contingency analysis, switchgear and transformer specification, SLD preparation, cable sizing, UPS sizing, substation layouts, protection scheme design, wiring modifications for EPC and M&E companies.

        • Power System Earthing
        • Earth potential rise (EPR) calculations and touch and step voltage calculations with either CDEGS or XGSLab, earthing layouts, soil resistivity testing, fall of potential tests, earthing inspections and resistance testing.

        • Power System Consultancy
        • Concept development and decarbonisation strategies, preparations of G99 and National Grid connection applications, review of ICP and vendor proposals, due diligence checks and client representative and failure investigations.

  • Case Studies
        • Team
        • As a consultancy our people are our greatest assets. Please follow the link above to meet the Aurora Team and find out more about us.

        • Careers
        • Are you interested in power system studies and analysis? Would you like to work for Aurora? If so click the above link to see our current vacancies.

  • News
  • Contact

G99 – Voltage Control

As part of G99 / Grid Code compliance studies, it is necessary to carry out a series of Voltage Control studies, and check performance stability. Voltage control is used in some parts of the UK, and common in Scotland, but it is not widely used in England or Wales.

Voltage control mode is a form of voltage-reactive power droop response. At nominal system voltage of 1.0pu, the generator reactive power output should be 0MVAr. When the system voltage falls, the generator should start exporting more reactive power, and if the voltage rises, the generator should start importing reactive power. The bounds of the MVAr output of the generator is 0.95PF lag to 0.95PF lead.

The allowable voltage droop range is between 2-7%, but in practice most operators would select a droop of 4% to 5%. At 4% droop, the generator would reach full MVAr output at system voltage of 0.96pu, and full MVAr import at a system voltage of 1.04pu. For example, a 50MW generator, experiencing a network voltage of 0.96pu would produce approximately +16.5MVAr, at 0.98pu it would be +8.25MVAr, at 1.02 it would be -8.25MVAr, and so on.

For Type B plants, there is no specific need, or expectation to operate in voltage control mode, and these generators have no performance requirements.

For Type C / D plants the voltage control response is built into the Power Park Controller, and the PPC is responsible for managing the network voltage. Interestingly, when compared to LFSM/FSM for frequency response, there are some very specific performance requirements for voltage control of the PPC, and some tuning of the PPC is often required.

The system studies required for voltage control are given in section C7.4 of G99, and section ECP.A.3.4 of the Grid Code. The two sections are virtually identical, but the Grid Code includes an extra scenario (v).


i) At maximum RC, and 0 MVAr (i.e. 1.0pu voltage), apply a negative voltage step to cause the system to reach maximum lagging PF (MVAr export).
ii) At maximum RC, and 0 MVAr (i.e. 1.0pu voltage), apply a positive voltage step to cause the system to reach maximum leading PF (MVAr import).
iii) At maximum RC, and 95% of lagging PF (MVAr export), apply a 2% negative voltage step to check stability.
iv) At maximum RC, and 95% of leading PF (MVAr import), apply a 2% positive voltage step to check stability.
v) At maximum RC, and leading PF (MVAr import), apply a negative voltage step to cause output to move to maximum lagging PF (MVAr export).

Interestingly, the requirement for (iii) and (iv) is to demonstrate control stability, rather than to a specific value – although this is obviously inferred as well.